Responsive image
博碩士論文 etd-0624108-143240 詳細資訊
Title page for etd-0624108-143240
論文名稱
Title
獨立風能及柴油發電系統之動態及經濟分析
Dynamic Simulation and Economic Analysis of an Isolated Hybrid Wind Diesel System
系所名稱
Department
畢業學年期
Year, semester
語文別
Language
學位類別
Degree
頁數
Number of pages
98
研究生
Author
指導教授
Advisor
召集委員
Convenor
口試委員
Advisory Committee
口試日期
Date of Exam
2008-06-12
繳交日期
Date of Submission
2008-06-24
關鍵字
Keywords
none
hybrid system, non-dispatchable, nature-dependent, economic analysis, MATLAB/Simulink
統計
Statistics
本論文已被瀏覽 5701 次,被下載 4224
The thesis/dissertation has been browsed 5701 times, has been downloaded 4224 times.
中文摘要
none
Abstract
An isolated hybrid system comprised of a dispatchable and a non-dispatchable power generation sources, is proposed to supply the load of a remote village in the west region of Haiti. The wind speed data and load data of this remote village are used to study the system. The non-dispatchable generation comes from a nature-dependent wind turbine, and the dispatchable one is a diesel generator. Using MATLAB/Simulink, dynamic simulations are performed to investigate the interaction between these two power sources for the load management, and the voltage and frequency behaviors during wind speed and load variations. Economic analyses of the
system are also conducted. The cost of energy (COE), energy payback time (PBT), internal rate of return (IRR) and avoided cost (AC) of CO2¬, NOx and PM (Particles Materials) of the hybrid system are computed, and results are compared with those of the baseline diesel only case. Simulation results show that the wind turbine and the diesel generator can be operated suitably in parallel, and the economic analyses show the positive benefits of wind generation in reducing COE and increasing the avoided
cost (AC) of emitted pollutions.
目次 Table of Contents
Chapter 1 Introduction ………………………………………………………1
1.1 Background …………………….………………………………………………1
1.2 Literature Review..…………………………………………………………….4
1.3 Motivation for this work and thesis outline……..……………………………6
Chapter 2 Wind and Diesel Power Generation System…………………8
2.1 Wind Turbine Modeling………………………………………………………9
2.2 Self Excited Induction Generator (SEIG) Modeling…..……………………..13
2.2.1 Induction Machine..……………………………………………………….14
2.2.2 Equivalent electrical circuit of Induction Machine……………………15
2.2.3 Self Excited Induction Generator………………………………………15
2.3 Diesel Generation System…..………………………………………………..30
2.3.1 Diesel Engine Model.…..………………………………………………...31
2.3.2 Synchronous Generator Model and Equivalent Circuit……………...34
2.3.3 Parameters identification…………………………………………………38
Chapter 3 Hybrid Wind-Diesel Generation System……………………41
3.1 Hybrid wind/diesel system…………………………………………….42
3.2 System frequency control……………………………………………….42
3.3 Control principle…………………………………………………………45
Chapter 4 Economic Analysis of the Hybrid Wind/Diesel System…..56
4.1 Energy Demand… …………………………………………………….……..56
4.2 Diesel Energy System………………………………………………….………59
4.3 Wind Energy System…………………………………………………………...60
4.4 Wind-Diesel System…………………………………………….……………...61
4.5 Hybrid System Spreadsheet Model……………………………………………62
4.6 Costs Analysis…………………………………………………………………64
4.7 Wind-Diesel Hybrid System Economics………………………………………66
4.8 Sensitivity Analysis……………………………………………………………68
Chapter 5 Conclusion and Future Works.……………………………….71
5.1 Conclusion…….……………………………………………………………….71
5.2 Future works………………………………………………………………….. 72
References…………………………………………………………………………74
Appendix A Block diagram of the hybrid system in MATLAB/simulink for the
simulations…………………………………………………………77
Appendix B System data for the economic analysis……………………………79
Appendix C Program used for the economic indices computation ………...…84
參考文獻 References
[1] F. Schweppe, et al. “Homeostatic utility control,” IEEE Transactions on Power
Apparatus and Systems, Volume PAS-99, No.3, May/June1980.
[2] MATLAB/Simulink, SimPowerSystems Documentation Available:
http://www.mathworks.com
[3] M. F. Gillie and W. E. Leithead “Operation and regulation of a wind and gas
virtual power plant,” 17th Intl. Conference Electricity Distribution, Barcelona,
May 2003.
[4] J. F. Manwell, J. G. Mc Govan and A. L. Rogers, Wind energy explained
Theory, Design and Application, John Wiley& Sons, 2002, ch.7.
[5] R. Hunter, and G. Elliot, (1994). Wind-Diesel Systems, Cambridge University
Press.
[6] M. R. Patel, Wind Power Systems, CRC Press, 1999, ch. 4-6.
[7] G. L. Johnson, Wind Energy Systems, 2001.
[8] A. D. Hansen, F. Iov, P. Sorensen, and F. Blaabjerg, “Overall control strategy of
variable speed double-fed induction generator wind turbine,” Proceedings of
Nordic Wind Power Conference, Chalmers University of Technology, Sweden
2004.
[9] W. Q. Jeffries, J. G. Mc Gowan and J. F. Manwell, “Development of a dynamic
model for no storage wind/diesel systems,” Wind Engineering, vol. 20, No. 1,
1996, pp 27-38.
[10] J. G. Slootweg, “Wind power: modeling and impact on power system dynamics,” PhD dissertation, Dept. Elect. Eng., Delft University of Technology, Delft,
Netherlands, 2003.
[11] D. Seyoum, C. Grantham and M. F. Rahman, “The dynamic characteristics of
an isolated self-excited induction generator driven by a wind turbine,” IEEE
Trans. Industry Applications, vol. 39, no. 4, pp.936-944, July/August 2003.
[12] M. H. Salama and P. G. Holmes, “Transient and steady-state load performance
of stand alone self-excited induction generators,” Proceedings, IEE-Elect. Power Applications, vol. 143, no. 1, pp. 50-58, Jan. 1996.
[13] S. S. Murphy, O. P. Malik and A. K. Tandon, “Analysis of self-excited
induction generators,” Proceedings, IEE, pt. C, vol. 129, no. 6, pp. 260-265,
Nov. 1992.
[14] N. H. Malik and A. H. Al-Bahrani, “Influence of the terminal capacitor on the
performance characteristics of a self-excited induction generators,” Proceedings,
IEE, pt. C, vol. 137, no. 2, pp.168-173, Mar. 1990.
[15] L. Quazene and G. Mcpherson Jr, “ Analysis of the isolated induction generator,” IEEE Trans. on Power Apparatus and Systems, vol. PAS-102, no. 8,
pp. 2793-2798, Aug. 1983.
[16] T. F. Chan, “Capacitance requirements of self-excited induction generators,”
IEE Trans. Energy Conversion, vol. 8, no. 2, pp. 304-311, June 1993.
[17] C. Grantham, D. Sutano and B. Mismail, “Steady-state and transient analysis of
self-excited induction generators,” Proceedings, IEE, pt. B, vol 136, no. 2, pp.
61-68, March 1989.
[18] C.M. Ong, Dynamic Simulation of Electric machinery, Printice Hall, 1998.
[19] Paul C. Krause, O. Wasynczuk and S. D. Sudhoff, Analysis of Electric
Machinery, IEEE Press, 2002.
[20] F. Katiraei and M. R. Iravani, “Power management strategies for a microgrid
with multiple distributed generation units,” Power Systems, IEEE Transactions
on, pp. 1821 – 1831, Nov. 2006.
[21] R. Gagnon, B. Saulnier, G. Sybille and P. Giroux, “Modeling of a generic
high-performance of no storage wind-diesel system using MATLAB/Power
systems block set,’’ European Wind Energy Association, Global Wind power
conference (2002).
[22] J. W. Black, M. Ilic, “Demand based frequency control for distributed generation, distributed power industry of the future,” IEEE 2002.
電子全文 Fulltext
本電子全文僅授權使用者為學術研究之目的,進行個人非營利性質之檢索、閱讀、列印。請遵守中華民國著作權法之相關規定,切勿任意重製、散佈、改作、轉貼、播送,以免觸法。
論文使用權限 Thesis access permission:校內校外完全公開 unrestricted
開放時間 Available:
校內 Campus: 已公開 available
校外 Off-campus: 已公開 available


紙本論文 Printed copies
紙本論文的公開資訊在102學年度以後相對較為完整。如果需要查詢101學年度以前的紙本論文公開資訊,請聯繫圖資處紙本論文服務櫃台。如有不便之處敬請見諒。
開放時間 available 已公開 available

QR Code