論文名稱
Title
敏感性設備受電壓驟降影響分析
Effect of Voltage Sags on Sensitive Equipment
系所名稱
Department
畢業學年期
Year, semester
語文別
Language
學位類別
Degree
頁數
Number of pages
83
研究生
Author
指導教授
Advisor
召集委員
Convenor
口試委員
Advisory Committee
口試日期
Date of Exam
2005-07-19
繳交日期
Date of Submission
2005-07-28
關鍵字
Keywords
電壓驟降、敏感性設備、電壓忍受曲線
Sensitive Equipment, Voltage Tolerance Curve., Voltage Sag
統計
Statistics
本論文已被瀏覽 5673 次,被下載 4954
The thesis/dissertation has been browsed 5673 times, has been downloaded 4954 times.
中文摘要
電壓驟降是由系統故障、過載或大型馬達啟動所導致之短時間電壓大小的下降。電壓驟降是許多敏感性設備跳機無法正常工作的主因,為了解一些與程控相關之設備的電壓忍受情形,本研究對一些電壓敏感的設備(個人電腦、AC電磁接點、高壓氣體放電燈及可程式邏輯控制器),進行壓降測試並建立他們的電壓忍受曲線。本研究參考IEC 61000-4-11所建議之電壓降幅及持續時間進行測試,利用測試結果之資料可估計不同用戶對電壓品質的需求及敏感性負載易受事故影響之區域範圍。
Abstract
Voltage sags are short duration of voltage reduction caused by system faults, overloads and starting of large motors. Voltage sags are the main causes of trips of various sensitive equipment. In order to understand the voltage-tolerance performance of some process control equipment, this thesis presents test results of some sensitive equipment (such as computers, AC contactors, high intensity discharge lamps and programmable logic controller) and provides their voltage tolerance curves. A number of magnitudes and durations recommended by IEC 61000- 4- 11 are used to perform the tests. With the performance information in hands, power quality requirements of different types of equipment and customer, and area of vulnerability for sensitive loads could be estimated.
目次 Table of Contents
目 錄

中文摘要 I
英文摘要 II
目 錄 III
圖 目 錄 V
表 目 錄 VII

第一章 緒論 1
1-1 研究背景與動機 1
1-2 國內外研究概況 2
1-3 論文大綱 4
第二章 電壓驟降及敏感性設備介紹 6
2-1 電壓驟降類型及特性 6
2-1-1電壓驟降 6
2-1-2電壓驟降類型 8
2-1-3電壓驟降特性 10
2-2 電壓驟降標準 13
2-2-1設備測試方面的標準 13
2-2-2設備忍受能力的標準 13
2-3 電壓驟降對敏感性設備之影響 16
2-3-1 電磁接點 16
2-3-2 可程式邏輯控制器 17
2-3-3 個人電腦 18
2-3-4 高壓氣體放電燈 20
第三章 電壓驟降忍受能力測試流程及儀器介紹 24
3-1 測試流程及設備簡介 24
3-2 測試步驟及方法 25
3-2-1 AC電磁接點測試程序 25
3-2-2 PLC測試程序 27
3-2-3 個人電腦測試程序 33
3-2-4 高壓氣體發電燈測試程序 37
第四章測試結果與討論 41
4-1 電磁接點測試結果 41
4-2 可程式邏輯控制器測試結果 44
4-3 個人電腦測試結果 47
4-4 高壓氣體放電燈測試結果 52
4-4-1 安定器型式對壓降忍受能力的影響 52
4-4-2 Point on wave對HID燈忍受能力的影響 53
4-4-3 燈泡新舊對HID燈壓降忍受能力的影響 54
4-4-4 燈泡種類對HID燈壓降忍受能力的影響 55
4-5 討論 57
第五章結論及未來努力方向 60
5-1結論 60
5-2未來努力方向 61

參考文獻 63
附錄A 靈敏性設備電壓驟降忍受能力測試認證 67
參考文獻 References
參考文獻

[1] McGranaghan, M.F., Mueller, D.R., Samotyj, M.J., “Voltage sags in industrial systems,” IEEE Transactions on Industry Applications Volume 29, Issue 2, pp. 397 – 403, March-April 1993.
[2] Melhorn, C.J., Davis, T.D., Beam, G.E., “Voltage sags: their impact on the utility and industrial customers,” IEEE Transactions on Industry Applications, Volume 34, Issue 3, pp. 549 – 558, May-June 1998.
[3] Koval, D.O., Hughes, M.B., “ Canadian national power quality survey: frequency of industrial and commercial voltage sags,” IEEE Transactions on Industry Applications, Volume 33, Issue 3, pp. 622 – 627, May-June 1997.
[4] IEEE Std 1346-1998, “Recommended practice or evaluating electric power system compatibility with electronic process equipment.”.
[5] STRI report , “Test and evaluation of voltage dip immunity ,” 2002.
[6] EPRI report, “Assessing power quality in a California processing plant,” 2003.
[7] Bollen, H.J., Understanding power quality problems, IEEE Press, 2000.
[8] Dugan, R.C., “Electrical power systems quality,” McGraw-Hill, 2003.
[9] Sarmiento, H.G., Estrada, E., “A voltage sag study in an industry with adjustable speed drives,” IEEE Industry Applications Magazine, Volume 2, Issue 1, pp. 16-19, Jan.-Feb. 1996.
[10] Strangas, E.G., Wagner, V.E., Unruh, T.D., “ Variable speed drives evaluation test,” IEEE Industry Applications Magazine, IEEE Volume 4, Issue 1, pp. 53-57, Jan.-Feb. 1998.
[11] Collins, E.R., Jr., Mansoor, A., “ Effects of voltage sags on AC motor drives,” IEEE Textile, Fiber, and Film Industry Technical Conference, May 1997.
[12] Keus, A.k., Abrahams, R., “Analysis of voltage sag testing results of a 15kw PWM adjustable speed drive.” IEEE International Electric Machines Drives Conf., Seattle, WA, May 9–12, 1999 IEEE 1999.
[13] Bollen, H.J., “Analysis of voltage tolerance of AC adjustable-speed drives for three-phase balanced and unbalanced sags.” IEEE transactions on industry applications, Volume 36, Issue 3, pp. 904-910, May-June 2000.
[14] Collins, E.R., Zapardiel, F., “An experimental assessment of AC contactor behavior during voltage sags,” Proceedings of the IEEE International Symposium on Industrial Electronics, 1997 ISIE '97, Vol. 2, pp. 439 - 444, 7-11 July 1997.
[15] Collins, E.R., “The impact of power system disturbances on AC-coil contactors,” IEEE Transactions on Industry Applications, Vol. 26, Issue: 3, pp. 556-562, May-June 1997.
[16] Pohjanheimo, P., Lehtonen, M., “Equipment sensitivity to voltage sags-test results for contactors, PCs and gas discharge lamps, Harmonics and Quality of Power,” 10th International Conference on Harmonics and Quality of Power, Volume 2, pp. 559-564, 6-9 Oct. 2002.
[17] Djokic, S.Z., Milanovic, J.V., Kirschen, D.S, “Sensitivity of AC coil contactors to voltage sags, short interruptions, and undervoltage transients,” IEEE Transactions on Power Delivery, Vol. 19, Issue: 3, pp. 1299-1307, July 2004.
[18] EPRI Report, “Performance and design evaluation of switch-mode power supplies - AC interface issues,” 1995.
[19] Djokic, S.Z., Desmet, J., Vanalme, G., Milanovic, J.V., Stockman, K, “Sensitivity of personal computers to voltage sags and short interruptions,” IEEE Transactions on Power Delivery, Volume 20, Issue 1, pp. 375-383, Jan 2005.
[20] EPRI Report, “Characterizing the impact of power quality on programmable logic controller with and without power-conditioning devices.” 2000.
[21] Dorr, D.S., Mansoor, A., Morinec, A.G., Worley, J.C., “Effects of power line voltage variations on different types of 400-W high-pressure sodium ballasts.” IEEE transactions on industry applications, Volume 33, Issue 2, pp. 472-476, March-April 1997.
[22] Short, T.A., Mansoor, A., Sunderman, W. A., “ Site variation and prediction of power quality,” IEEE Transactions on Power Delivery, Volume 18, Issue 4, pp. 1369-1375, Oct. 2003.
[23] European Standard EN-50160, “Voltage characteristics of electricity supplied by public distribution system,” CENELE, Brussels, Belgium, 1994.
[24] IEEE Std 1159-1995, “IEEE Recommended practice for monitoring electric power quality,”.
[25] Abdelhak M. Z., Ow, j. k., “Power quality issues on the distribution system,” Curtin University of Technology Electrical Engineering Project 2002.
[26] IEC Standard 61000-4-11, “Electromagnetic compatibility (EMC) - Part 4-11: Testing and measurement techniques - Voltage dips, short interruptions and voltage variations immunity tests,” IEC Press, 2001.
[27] ITIC (CBEMA) Curve application note, information technology industry council, 2000.
[28] SEMI F47, “Specification for semiconductor processing equipment voltage sag immunity.”
[29] 工業技術研究院,“低功率複金屬燈與週邊裝置-先期投資可行性分析,”2004。
[30] Collins, E.R., “A three-phase sag generator for testing industrial equipment,” IEEE Transactions on Power Delivery, Volume 11, Issue 1, pp. 526-532, Jan. 1996.
[31] “For electrical lamps-Metal halide lamps - Method of measuring characteristics,” American National Standard Institute, New York, ANSI C78.387-1995, 1995.
[32] 林再福,“複金屬燈特性研究及電子安定器設計”,國立中山大學電機工程學系博士論文,中華民國九十一年。
電子全文 Fulltext
本電子全文僅授權使用者為學術研究之目的,進行個人非營利性質之檢索、閱讀、列印。請遵守中華民國著作權法之相關規定,切勿任意重製、散佈、改作、轉貼、播送,以免觸法。
論文使用權限 Thesis access permission:校內校外完全公開 unrestricted
開放時間 Available:
校內 Campus: 已公開 available
校外 Off-campus: 已公開 available


紙本論文 Printed copies
紙本論文的公開資訊在102學年度以後相對較為完整。如果需要查詢101學年度以前的紙本論文公開資訊,請聯繫圖資處紙本論文服務櫃台。如有不便之處敬請見諒。
開放時間 available 已公開 available

QR Code